iCobus Telecommunications and Data Cabling Recruitment Agency

iCobus - ICT, Telecoms, Cabling Recruitment  iCobus - ICT, Telecoms, Cabling Recruitment  iCobus - ICT, Telecoms, Cabling Recruitment  iCobus - ICT, Telecoms, Cabling Recruitment

Tel : 0208 544 0944
admin@icobus.com

Latest News

 

Category 8 cable will play a major role in 25G and 40G data center Ethernet

How the TIA and IEC committees created new standards for Category 8 cable testing devices

By the end of 2016 several cabling manufacturers are expected to release their initial Category 8 cable products. Representing the next generation of twisted pair cabling, Category 8 supports bandwidths of up to 2GHz and will be used initially in data centers for 25G and 40Gb Ethernet for distances of up to 30 meters (100 feet).

Additionally, cable testing manufacturers will shortly release new Category 8 field testing devices, enabling contractors to test and verify the real-world performance of Category 8 cabling, and to obtain the warranty from the cabling manufacturer for the end-user.

"Category 8 will play a major role in data centers and mission-critical environments upgrading to 25/40GBASE-T, says Mark Dearing, Senior Product Manager at Leviton. "Cabling manufacturers are now engineering solutions with additional quality and flexibility to meet these demanding new applications. But even the most advanced infrastructure relies on high-quality installation practices to ensure the network will operate at its best. Proper testing and certification in the field translates to less chance of disruption, downtime, and unforeseen costs in the future."

How it was done
In 2011, TIA first submitted the Project Authorization Request (PAR), the official "Call For Interest" for next-generation cabling (with "cabling" defined as the cable and connector together). This prompted cable manufacturers to begin developing Category 8 prototypes and prompted the ANSI/TIA and ISO/IEC committees to begin developing new standards for Category 8 cabling and field testing devices.
The TIA and IEC committees are made up of representatives from cable, cabling system, and field testing manufacturers, as well as installers and users of cabling systems. While many of these vendors are market competitors, it benefits them to work together to develop a common set of product standards. This ensures that all Category 8 cabling will offer the same performance levels, regardless of manufacturer, and all Category 8 field testers will certify all Category 8 cabling using agreed performance measurement levels.

The committees developed the standards over several years. The results are:

·         ANSI/TIA-568-C.2-1, an addendum to the established 568-C.2 standard for balanced twisted-pair cabling, includes requirements for Category 8 cabling and components.  Both these documents will be included as part of the next issue of the 568 series (568-D.2, expected in 2017).  ISO/IEC 11801, the international equivalent of these standards, is also being updated with Class I and Class II cabling parameters.

·         ANSI/TIA 1152A, an update to the 1152 standard for field test instruments used to test balanced twisted-pair cabling, was approved for publication in October 2016, and provides specifications for instruments used to test Category 8 cabling. (IEC 61935-1, the international equivalent of the testing standard, is also being updated.)

Developing the testing standards
It's important to understand that testing Category 8 cabling is not just a matter of increasing the upper frequency of the testing module. In addition to a higher frequency range, Category 8 cabling requires tighter performance specifications in the tester, and new adapters capable of supporting that performance.
To develop Category 8 field testers, manufacturers and committee members developed new requirements and testing methodologies, including:
·         Test fixtures specified up to 2 GHz, for use in laboratory test environments
·         An RJ45 reference plug specified to 2 GHz.
·         Cable and connector performance requirements
·         Products to test

Laboratory test fixtures
To develop a standardized cable tester, the TIA and IEC committees first had to agree on standards for testing Category 8 cabling in a lab environment. This required them to develop test fixtures to connect Category 8 cabling to a Vector Network Analyzer. (The VNA is the "yardstick" against which the final testing device is compared, to ensure the tester gives accurate measurements.)



The fixture in Photo #1 connects Category 8 links and components to the VNA. This fixture was developed in conjunction with the TIA and ISO committees, and was created to handle frequencies up to 2 GHz.
The TIA 1183-1 standard for test fixtures was published in January, 2016. Since cable testing manufacturers may create their own version of the lab test fixtures above, the requirements for the fixtures themselves had to be standardized. The goal of this standard is to ensure that all test fixtures created by all cable testing manufacturers will connect to their VNAs in a way that yields accurate and consistent measurements when testing Category 8 cabling samples or RJ45 plugs from different cabling manufacturers.

 

Standardized RJ45 plugs
A standardized RJ45 plug is required to perform field measurements. These test plugs have a very tightly-controlled electrical performance, and allow for consistent and accurate measurements of jacks and links from multiple manufacturers. The "Jupiter" RJ45 plug, developed through a joint effort between cabling and cable testing manufacturers, was used as an industry-wide reference for testing Category 8 cabling and components.




Photo 2 shows (1) the original "Jupiter" tip, (2) the "Jupiter" tip installed inside a permanent link adapter (open), and (3) the assembled permanent link adapter, which is a component of the field testing device.
Laboratory test plugs are usually treated with great care, and patch cord plugs may only be inserted a few times. But field tester plugs will be inserted thousands of times, whenever the contractor uses the device for a field test. Therefore, each testing manufacturer must design a version of the plug and jack that will be rugged enough for repeated in-the-field use.

 

Cable and connector performance requirements
The TIA and IEC standards for Category 8 cabling and connectors had to be finalized to a certain degree, so the testing manufacturers would know which performance metrics to measure in the Category 8 cabling tests. Once the standards were finalized, testing manufacturers were able to accurately test Category 8 cabling prototypes using those metrics, which aided them in developing their final testing products.

 

Final Approval
As a "final step" before product release, testing manufacturers submit their Category 8 field testers to the cabling manufacturers for approval. The cabling manufacturers test their Category 8 cabling, first with a field tester, then with a VNA, and compare the tests to ensure that both devices get the exact same results. This proves the field tester can accurately measure Category 8 cabling according to the same performance requirements as a laboratory VNA, allowing the cabling manufacturers to confidently provide warranties for installations certified with these testers.

Certain performance requirements (i.e. transverse conversion loss, resistance unbalance between pairs) have been specified for the first time in Category 8 cabling standards. While these tests are required for cabling and components, they are considered optional tests for installed cabling, due to their complexity. Contractors aren't required to perform them when certifying Category 8 cabling for the warranty. But if contractors have a Category 8 tester that can test to these requirements, it's highly recommended that they include these tests. A full range of tests will provide better peace of mind for their clients that the installed Category 8 cabling is working properly, and can handle the client's applications.

By creating these standards, we've helped to ensure these products will work as intended in their "real world" applications, regardless of who manufactures them.

Read more on:
http://www.networkworld.com/article/3143764/lan-wan/category-8-cable-will-play-a-major-role-in-25g-and-40g-data-center-ethernet.html